How many CFM per ton of cooling? The 400 CFM rule of thumb

Where 400 CFM per ton comes from, why humid and dry climates use 350 or 450, and how the number sets the airflow your ducts must carry.

Quick answer: the usual rule of thumb is about 400 CFM of airflow per ton of cooling. A 2.5 ton system gets about 1,000 CFM and a 3 ton system about 1,200. Energy Vanguard puts the range at 300 to 350 CFM per ton in humid climates and 450 to 550 in dry ones, and ACCA warns that it is “not always the case”. Use the equipment maker’s tables when you have them. The rule is a starting point for sizing ducts, not a design.

What the number means

A ton of cooling is 12,000 BTU per hour. CFM is cubic feet of air per minute. So “400 CFM per ton” means the system moves 400 cubic feet of air across the coil each minute for every 12,000 BTU/h of capacity. Multiply the tonnage by 400 and you have the total airflow the ducts must carry.

Where the number comes from

The sources are clear about the physics and vague about the origin of 400 itself. ACCA’s physics post derives the sensible heat equation:

BTU/h = 1.08 x CFM x ΔT

Here ΔT is the temperature change of the air across the coil. The 1.08 is air density (0.075 lb per cubic foot) times the specific heat of air (0.24 BTU per pound per degree) times 60 minutes per hour. Rearranged, CFM = BTU/h / (1.08 x ΔT).

Now apply it to one ton. ACCA’s post notes that one ton at a 20°F temperature change needs about 555 CFM if every BTU were sensible cooling. But air conditioners also remove moisture, which is latent cooling, and that heat does not change the air temperature. So less than the full 12,000 BTU/h is sensible.

Here is our arithmetic, not a figure from any source. If about 75 percent of the cooling were sensible, which is our assumption, one ton would do 9,000 BTU/h of sensible cooling. At 400 CFM, that is a temperature drop of 9,000 / (1.08 x 400) = about 21°F. That is close to the 20°F used in ACCA’s example. The ACCA post does not give this derivation and does not explain where 400 originates, so treat it as a plausible link, not a proof.

Why it changes by climate

Airflow does not only change how much air you move. It changes how the cooling splits between cooling the air and drying it. Energy Vanguard says “slower air means colder air” and “slower air means drier air”, so humid climates want less airflow, 300 to 350 CFM per ton, and dry climates want more, 450 to 550.

ACCA’s blog shows the effect for a 2.5 ton unit at the same conditions (75°F indoors, 75°F outdoors, 63°F entering wet bulb):

Airflow CFM per ton Total capacity Sensible share
875 CFM 350 29,500 BTU/h 52%
1,000 CFM 400 29,800 BTU/h 58%
1,125 CFM 450 30,300 BTU/h 61%

More airflow gives a little more total capacity and a larger sensible share. ACCA recommends following the manufacturer’s data over any rule of thumb and says wrong airflow can reduce performance.

When 400 is the wrong number

  • Altitude and unusual temperatures. The 1.08 assumes standard air, near sea level and room temperature. ACCA’s post says to adjust it when the air is thinner.
  • Humid or dry climate. Use the ranges above as a guide.
  • Equipment data. The unit’s published performance tables beat any rule. ACCA says to leave the maker’s data with the indoor unit so technicians can check the system later.
  • Variable-speed equipment. We did not research it, so check its documentation.

How the number sets duct size

Total airflow is the starting point for the ducts. Say a 2.5 ton system at 400 CFM per ton needs 1,000 CFM. Our 6 inch duct chart shows that one 6 inch round duct carries about 118 CFM at 600 feet per minute. This is an illustration only: 1,000 / 118 is about 8.5, so roughly nine 6 inch runs would be needed at that velocity. A real design uses a trunk, branch runs and a pressure budget, and friction and fittings change the answer. See how much CFM a 6-inch duct can handle for the numbers and why charts disagree, and round to rectangular duct equivalent diameter if your trunk is rectangular.

HVAC Duct Design, one of our apps, sizes round and rectangular ducts from airflow. Its values are estimates, so confirm a real installation with a load calculation and the equipment data.

Frequently asked questions

How many CFM per ton of cooling?

About 400. Energy Vanguard gives 300 to 350 for humid climates and 450 to 550 for dry ones. ACCA says 400 is a common rule of thumb but not always right.

How do I work out CFM for a 3 ton system?

Multiply the tonnage by 400. A 3 ton system comes to about 1,200 CFM. Use the manufacturer’s tables if you have them.

Where does the 1.08 come from?

It is air density (0.075) times specific heat (0.24) times 60 minutes. The equation BTU/h = 1.08 x CFM x ΔT is for sensible cooling at standard air conditions.

Why do humid climates use less airflow?

Slower air gets colder and drier as it passes the coil, so it removes more moisture. Dry climates use more airflow to deliver more sensible cooling.

Does CFM per ton set the duct size?

It sets the total airflow, which you then split among the runs. The size of each run depends on the velocity or friction rate you design to.

Sources

  • ACCA HVAC Blog, The physics of heat and air flow: the derivation of 1.08, the sensible heat equation, the 555 CFM per ton figure at a 20°F temperature change and the standard-air assumption. Opened.
  • ACCA HVAC Blog, 400 CFM per ton, or is it?: 400 as a rule of thumb that is not always right, the 350, 400 and 450 comparison and the advice to use the maker’s data. Opened. It does not explain the origin of 400.
  • Energy Vanguard, What’s the correct air flow for an air conditioner?: the nominal 400 and the humid and dry climate ranges, and “slower air means colder air”. Opened.
  • Green Building Advisor’s article on airflow and ACCA Manual S gives the same ranges and ties them to Manual S. Opened, but not relied on beyond that. We did not read Manual S itself.